Category: Iacdrive_blog

DC Motor Armature Testing

For a DC Motor Armature, There is a simple method of determining the condition of the Armature.
Drop Test Method: Give a DC Voltage across the commutator Segments for one pole pitch area from a Power supply or Battery. Connect Positive end of the DC power supply at one end and the Negative end at the opposite end.
For example if the total number of commutator segments are say, 40 in the armature to be tested and the total number of poles is 4, then one pole pitch area will be 10 segments.

Now measure with a Milli volt meter say 0 to 10 millivolts range, the Voltage Drop at the center point, that is between 5th and 6th segment. again rotate the Armature Clockwise or Anti clock wise and measure the next set of segments.
Like this complete measurements for all the 40 segments pairs. simultaneously recording the readings.

If there is any defect in the winding, that is shorted or open, it will show in the readings.
If the reading of Milli volt Meter is uniform for the all the 40 segments pairs, than the armature is good. If there is short between winding or the winding coil between one particular pair of segments, the reading will be less drop in millivolts. If there is any loose or open, the reading will be more than normal readings. Thus one can determine the condition of a DC armature for short or lose or open winding.

When testing a DC armature there is a series of tet should that should be done. The first is. Ground insulation test or more commonly known as a mugger test, usually done at 500VDC. If the ground reading is above 1 meg ohm the armature is good to go to the next test which is a bar to bar test. There are 2 pieces of equipment to conduct this test the best. One of these combined with the mugger test will tell you if the armature is satisfactory return to service. The first bar to bar test is conducted with a “DLRO” digital low resistance ohm meter. The meter will circulate about 8-10 amps thru adjacent successive bars and measure the milli ohm resistance of the circuit. If there is more than a 5% variation then the armature is shorted turn to turn. The next tester which is called a high frequency bar to bar tester. The tester has 4 tet points and as you move it around the armature a high frequency voltage is introduced across the pairs of successive windings and the meter will show a variation if there is a shorted turn. If it passes either of these 2 bar to bar test and the ground insulation test then it can be returned to service.

Ratio of stator coils and rotor poles in three phase axial flux PM motor design

Question:
I am currently investigating the design of a three phase axial flux PM motor, but replacing conventional materials with high temperature superconductors. I’m interested to know the thoughts of group members regarding design rules/rules of thumb relating to the number of stator coils and rotor poles. Many in the amateur wind turbine community seem to use a 4:3 ratio (magnets:coils), but I can’t seem to find anything ‘official’ on the topic.

An equal number of magnets: coils would cause problems with starting the motor and with cogging/torque pulsations.
The only textbook I’ve found dedicated to the design of axial flux PM motors is Jacek Gieras’s book on ‘Axial Flux Permanent Magnet Brushless Machines’, but this seems only to mention examples of coils: poles ratios (e.g., 12 stator coils and 8 rotor poles, 9/8, etc.).

Answer:
“Design of Brushless Permanent-Magnet Motors” by J.R. Hendershot Jr. and TJE Miller is an excellent design book and pages 3-50 thru 3-55 illustrate the 3 phase winding patterns you describe (8/6, 8/9, and 4/6). Whether axial air gap or radial air gap the principles are the same. I assume with an axial air gap machine you do not want phases overlapping each other, that is the common factor in the three patterns above. This keeps winding simple and compact and is commonly used on smaller 3 phase brushless motors.

These windings do not automatically guarantee a true BEMF sine wave form. If you want a sinusoidal waveform you will have to do some work on tailoring the magnetic design (gap between magnets, skewing, air gap profiling, etc.). Some servo motor manufacturers do just this to get a true BEMF sine wave to match their sine wave controllers for ripple free torque operation.

Another decision is does the coil center have a laminated steel pole or only and air center. Air gap windings should be axially thin and have no hysteresis component which is good for high speed operation. A slotted pole winding can handle more wire bulk but a laminated construction may be difficult to implement, you might look at an AC Powdered Metal for the Armature and teeth.

If you allow phase coils to overlap there are a great many other winding patterns possible (listed in the reference book), some are better for Trapezoid controller drive and some are better for sine wave controller drive (BEMF should match controller drive type). Just depends on you end goals.

AC motors Variable torque and Constant torque

AC Motors – Variable torque: AC motors have a speed torque characteristic that varies as the square of the speed. For example, an 1,800/900-rpm electrical motor that develops 10 hp at 1,800 rpm produces 2.5 hp at 900 rpm. Since ac motors face loads, such as centrifugal pumps, fans, and blowers, have a torque requirement that varies as the square or cube of the speed, this ac motor characteristic is usually adequate.

AC Motors – Constant torque: These ac motors can develop the same torque at each speed, thus power output varies directly with speed. For example, an ac motor rated at 10 hp at 1,800 rpm produces 5 hp at 900 rpm. These ac motors are used in applications with constant torque requirements such as mixers, conveyors, and compressors.

Add a separate AC line reactor/DC choke to VFD

How to add a separate AC line reactor / DC choke in case the variable frequency drive doesn’t have it? Can we use a separate line reactor if it’s not built in with the VFD drive? What all parameters I would have to look into, if I want to add the line reactor? Is there any sizing criteria? How would I have to install it?

It depends on how much THD you want to have and how much money you want to spend. If this is for electric motor protection there are additional methods of spike suppression and better reactors/filters.

Size for amps and voltage.

THD will vary will design and specifications. You want the reactor to filter or tune out the unwanted frequencies, mainly the AC drive carrier frequency. One often overlooked parameter is what rejection frequency the reactor is wound for. You want a reactor wound for the rejection frequency you have your VFD drive set at.

This will make you want to raise the carrier frequency to make the reactor smaller, less turns, and less expensive. Before you do this look at the de-rating tables and other factors involved with a high carrier frequency.

It’s always best to first check with your VFD installation and operation documentation. It is likely that the motor drives manufacturer makes recommendations for reactor ratings. That said 3 to 5% reactance at the VFD drive’s rated input current is always a good solution. If there is no internal bus choke or reactor in the VFD then use 5%. Don’t sweat the voltage drop. The drop is in quadrature to the source voltage and so mostly subtracts at a 90 degree angle. Thus, the drop will be less than half the %reactance.

DC Chokes on variable frequency drives

From a manufacturing economics standpoint, there is often a trade off in the decision to add a DC bus choke or not based on its ability to reduce the DC bus ripple. This is because it can reduce the DC bus capacitance necessary to present a clean DC source to the transistors. For some AC drive manufacturers who have the internal capability to wind their own component chokes, this often represents a component cost benefit compared to buying capacitors from outside vendors and being more subject to market volatility. On the other hand if the AC drive manufacturer IS also a manufacturer of capacitors, it works exactly the other way around.

I believe this is why we often see small component class drives being made without DC chokes primarily by companies, mostly in Asia, for whom capacitors are a very low cost commodity. When EU and US manufacturer make larger variable frequency drives, it’s usually less expensive for them to wind chokes, but that option is often perceived to be too physically large for component class drives so they farm out their designs and production to Asian manufacturers. Ironically then, users will add an external AC reactor anyway, but fail to observe that the overall footprint is now larger than it would have been with a DC choke.

I attribute this to the same false market perception that society uses in buying airline tickets. We now shop on the internet based on one criteria, price of the ticket. The airlines have finally figured that out, so they now appear to have lower ticket prices, but charge us extra for bags, snacks, leg room etc. and we actually are paying MORE than we used to. So to relate that back to the AC drives, the market demanded smaller and smaller packaging of VFD drives, which became a primary selection criteria, leading to the smallest physical package, the ones without DC chokes, being dominant in that low kW realm to the point where virtually everyone else gave up and joined the party.

That said, there is still validity to the added protection for the front end of the AC drive provided by the reactor compared to a DC choke. If there are multiple AC drives in an enclosure however, that benefit can still be realized with one larger reactor ahead of the entire inverter drive input power circuit.

Compensate electric motors effect of high altitude

Case: Two electrical motors that design for altitude <1000 m but now this two electrical motor have installed on altitude 1880 m and this electrical motors become very hot. The electrical machines power is 15300KW & 9700KW and they cooled by force air and water cooler.

First – machines designed for higher-than-normal altitude (i.e. in excess of 1000 m = 3300 ft above sea level) are designed with lower allowable temperature rises. The rule-of-thumb approximation is 1 degree C for every 100 m above 1000.

This means a typical Class B rise (max 80 C over 40 C ambient) will be designed for a max 71 C rise over ambient at 1880 m altitude.

Since temperature is more-or-less proportional to the square of the current, the design either reduced in output power to limit the current, or is “overdesigned” so that the resultant output power is the effective de-rate condition. In this case, the “sea level” rating of 15300 kW would become 15300 * (71/80)^2 = 15300 * 0.94 = 14382 kW. Likewise, the 9700 kW machine would be rated for 9118 kW.

The ability to cool the machine effectively is based on two things: the amount of coolant in direct contact with the heat source(s), and the pressure of the coolant flow. At altitude, the density of the coolant is reduced significantly, hence the requirement to operate at lower power ratings. The pressure of the airflow over the windings, etc is ALSO reduced at higher altitude, making the cooling more inefficient.

Speeding up the blower (i.e. going from 6 pole speed to 4 pole speed, for example) will overcome some of this by increasing both airflow and pressure. However, the power draw on the blower drive motor may also necessitate an increase in size to accommodate the new loading parameters (including the effects of high altitude on it!). Note that if the air movement within the machine enclosure is dependent solely on the MACHINE rotor speed (i.e. a shaft mounted fan), there will be a need to develop and apply a separately-powered fan to accommodate the required changes.

The probability of voltage breakdown / corona / flashover is increased above 1800 m as well, which means at least taking a cursory look at both creepage and strike distances.

And finally – if, after all this, the machine is still overheating … time to look at the cleanliness of the liquid side of the heat exchanger. This may mean cleaning or replacing the tubing and headers, determining liquid flow rates (and pressures) and ensuring they are within original design criteria (roughly 3.8 litres per minute for each kW of loss in the rotating machine).

What’s PG card in variable frequency drive?

PG is short for Pulse Generator, generally it is used for measuring rotational speed. The most common PG card is optical encoder.
PG card is a part of vector variable frequency drive, to convert the encoder different form signals to suitable for the controller, like: electrical level conversion, analog digital conversion, optical isolation, etc.
Vector control variable frequency drive is a high-performance drive which can be comparable with DC converter.
In the vector control, it requires a motor speed feedback to the variable frequency inverter drive, this speed feedback is achieve by adding a rotary encoder (PG) to the motor, which means PG card feedback vector control VFD. In order to simplify the system, the feedback can be formed by operation of the inverter output signal, this control is called none PG card feedback vector control VFD, the performance has a slight gap than PG card feedback, but configuration is simple.

129 slot 48 Pole combination in motor design?

Koil can make the synthesis (i.e. design the winding layout from slot-pole combination) only for symmetrical windings. To have a symmetrical 3-phase winding the back EMFs must be equal and out of phase of 120 electrical degrees. Looking at the star of slots, this means that the spokes in the star (or phasors, one for each slot) must be equally spaced and the number of spokes must be multiple of the phase number.

Considering this example, the machine periodicity t is computed as:
t= HCF{Q,p}=HCF{129,24}=3.
Then the number of spokes in the star of slot is Q/t=129/3=43.

In order to have a balanced winding (assuming m=3 as number of phases) Q/t must be divisible by 3. Such condition can be written in general as Q/(m t) integer.

In this case we have Q/(mt)=129/(3 3)= 129/9=14.333 which is not integer, so that the winding is not symmetrical as here described.
Maybe there are some different/non standard arrangement of the winding.

Motor Rotor Bar issue in Current Signature Analysis

The condition of the rotor bars will determine how much torque your motors will deliver. As a person who has been in the electric motor repair business all my life it is something I constantly check. Normally when you talk about rotor bar health it refers to open rotor bars however I have found that in aluminium die-cast rotors there can be voids in the end-rings. Todays vibration equipment and your CSA equipment is so sensitive that it will pick up these voids. In a repair shop environment and with a motor with a good stator winding it is relatively simple to check for open rotor bars. if at all possible we will check for open rotor bars before we take a motor apart by performing a single phase rotor test. You apply approximately 20% of line voltage to two phases of the motor. Rotate the rotor through 360 degrees and monitor the current. If the current is steady the rotor is in good health. If you have one or more open rotor bars the current will drop as the open bars pass the energized part of the stator. A 10% swing would indicate open rotor bars.
Just in case there is a second cage in the rotor you can also put a voltmeter across one of the energized phases and the open phase. Just like the current, the voltage should stay steady.
When a motor is developing open rotor bars it will become noisy on start up. Noisier with each bar that becomes open. It can sound like a cement mixer or as if there is no lubrication in the bearings.

I have no idea what a rotor bar health index is. I would assume that it is a severity level that has been developed by the people who manufacture your test equipment.

Neither am i familiar with the Motor Current Signature Analysis. We use a surge tester which has an attachment for checking rotors but I don’t put much faith in it.

Open rotors can be a nightmare for electric motor repair facilities. Open rotor bars are not always visible and can be very difficult to detect. Our core tester has clamps that allow us to induce a low voltage and high current into the rotor cage but it is not conclusive. We could use a growler to energize the rotor and throw iron filings over the core. On a big rotor it takes a bit of time and customers don’t like paying for it, especially when you don’t find any problems.

If your motors are die-cast aluminium and they are starting up every day without struggling to get up to speed and they are not noisy during start up, your equipment might be picking up voids in the aluminium.
If you have copper or copper aloy rotors with brazed end-rings and I might suggest that you be concerned. Once you get one open rotor bar it only gets worse as time goes by.

SCR broken failure in soft starter

SCR’s are limited to a maximum current rating, as well as a maximum voltage rating. In addition, the number of starts per hour is also limited. A combination of voltage spikes, too many starts per hour, or too much current during a start will destroy a soft starter. Phase imbalance for either voltage or current will cause an SCR to fail, as will a single phase condition on a 3-phase motor. What also needs to be considered is the load being started. If it is a high starting torque load it may require a heavy duty version of soft starter to get it going.

SCRs rarely “break” but they do short out, or rather, become full time conductors. The only thing that can cause this is excess tightening torque or clamping pressure. If on the other hand that the soft starter is giving an indication that one SCR is shorted, then that is where the comments from Terence Smith come to play. It will be either a voltage spike, a current spike, or excess heat caused by excessive starting current or starts per hour.

But reactors will not really help and will increase the throughput losses in the soft starter, I would not waste time on that. Starting a spinning motor is not an issue with soft starters either. Both of these are potential issues with VFD, totally different animal.

If the SCR fault covers the unbalanced starting current too, there is another possibility. At the motor connection box, on the side of the motor there are 6 bolts with screws, for connecting cable, star-delta cooper sheets, and motor coils. The lowest places on the bolt are the clamps of the motor coils, which is followed by a bolt. Over this bolt there are the star-delta sheet, bolt, cable connection clamp and upper the 3-rd bolt. In many cases the lowest screw, at the coil clamp is not tight enough. The maintenance electricians never check them, because it doesn’t belong to the cable installation. In many cases they occurred output phase fault in inverters and phase faults in soft starters.